X5200 Ultraviolet Infrared Flame Detector
UVIR detector for complex detection environments
- X-Series Flame Detectors with Pulse Output
- X2200, X5200, X9800 Safety Manual
- X-Series Flame Detector Mounting Arm and Collar Attachment
- NF-SSI Certified Addendum for X2200, X5200G and X9800 Flame Detectors – Instructions
- X5200 UVIR Flame Detector – HART Communication Addendum
- X5200 UVIR Flame Detector – Instructions
UVIR detector for complex detection environments
The X5200 UVIR hydrocarbon flame detector can be configured to satisfy third-party requirements for rapid detection or for applications where extraneous IR radiation sources may cause other detectors to generate false alarms.
Features
- Multiple sensitivity modes
- Optical Integrity (oi®) performs automatic fail-safe checks every 60 seconds
- Heated optics for adverse environments and weather
- Data logger with event time and date stamping (1500 events)
- Can be configured to alarm to individual UV or IR sources
- Can meet NFPA 15 Ultra-High-Speed requirements (when properly configured and used in an EQP/HSDM safety system)
Technical Specifications
- Multiple communication protocols, including 0-20 mA, relay, Modbus, HART, FDT®/DTM and Eagle Quantum Premier® (EQP) safety system
- Diagnostic LED for local alarm and simple fault identification
- Large capacity event log storage (1,500 events)
- HART capable
- Copper-free aluminum or 316 stainless steel enclosure