Det-Tronics- Carrier Corporate

CTX10 Combustible Gas Transmitter

ATEXCSADet-Tronics Point IR Termination Box (PIRTB) FM ApprovalIECExSIL 2 Certification

Combine the CTX10 with combustible gas sensors to create a stand-alone gas detector

The model CGS sensor when used with the CTX10 is a catalytic combustible gas detector, provides continuous monitoring of combustible hydrocarbon gas and combustible hydrogen gas concentrations in the range of 0% LFL to 100% LFL. The CTX10 is third-party performance approved for methane and propane gases.

Features

  • Onboard magnetic calibration/reset switch for non-intrusive calibration capability
  • Compatible with constant current Det-Tronics catalytic sensors
  • Direct field replacement for Det-Tronics Model 505 Transmitters
  • Current level indicates fault condition and calibrate mode
  • Sensor sensitivity check
  • Suitable for use in a wide variety of combustible gas detection applications
  • Available in 316 stainless steel and black epoxy aluminum (shown)
  • Explosion-proof junction box available in aluminum or stainless steel

Technical Specifications

  • INPUT VOLTAGE—
    • 24 Vdc Nominal, Operating range of 18 - 30 Vdc Ripple cannot exceed 0.5 Volts P-P
  • POWER CONSUMPTION—
    • 4.0 watts maximum
  • PEAK STARTUP CURRENT—
    • Less than 0.5 ampere for < 0.2 second at 10 Vdc input, and less than 0.2 ampere for < 0.2 second at 24 Vdc input.
  • OUTPUT CURRENT—
    • Linear 4 to 20 mA
  • CURRENT LEVEL—
    • Calibration Fault: 1.6 mA
    • Other Faults: 1.0 mA
    • Calibration Mode: 2.0/2.2 mA in Infiniti mode, 3.4 mA in 505 mode
  • Three LEDs provide the following visual annunciation at the device:
Color Function/Indication
Green Power
Yellow Calibration, Faults
Blue End of life

This site uses cookies. By continuing to use this site you are agreeing to use cookies. Find out more about our privacy policy.